User manual ver. 20200927
The document presents collected information on safety, assembly and use of AURATON Aquila R.
24-Hour Wireless Thermostat
AURATON Aquila R is a daily wireless temperature regulator.
U | FrostGuard function to protect against freezing of the room. |
& | Possibility of cyclic lowering the programmed temperature by 3 °C for a period of 6 hours. |
LCD | Backlit LCD display The backlit display makes it possible to monitor the device’s operation even in poorly lit rooms. |
Description AURATON Aquila R
24-Hour Wireless Thermostat (transmitter)
On the front panel of AURATON Aquila R, there is a backlit LCD display and three function buttons.
- LCD display
- Temperature increase button
- Temporary temperature reduction mode buttons
- Temperature decrease button
- Pairing buttons
- Approval or on/off button. AURATON Aquila R
d |
|
Display
- Temperature
In normal operation mode, AURATON Aquila R displays the temperature of the room in which it is installed. - Temperature unit (R)
Indicates that the temperature is displayed in degrees Celsius. - Temporary temperature lowering mode indicator (T)
Active during a temperature cutback timer program. - Temporary temperature lowering mode programming indicator (S)
It indicates that the user has enabled temporary temperature lowering mode. Visible when the mode is not in effect, but the temporary temperature lowering function is active (for more information see the chapter “Setting the temporary temperature lowering mode”). - Transmission symbol (W)
It indicates communication with the receiver. - Battery depletion (X)
Indicator visible when the minimum acceptable battery voltage is exceeded. Replace the batteries as soon as possible.
Choosing the right location for AURATON Aquila R
The correct operation of AURATON Aquila R is largely influenced by its location. Using the device in a place with no air circulation or a place with direct sunlight may result in incorrect temperature control. AURATON Aquila R should be installed on the internal wall of a building (a partition wall), in an environment with free air circulation. You should avoid proximity to heat-emitting devices (TV, heaters, refrigerators) or locations exposed to direct sunlight. The vicinity of doors and exposing AURATON Aquila R to possible vibrations may also cause problems with proper operation of the device.
Battery installation/replacement
The battery sockets are located inside AURATON Aquila R on both sides of the display. To install the batteries, remove the AURATON Aquila R housing as shown in the figure.
Insert two AAA 1.5V batteries into the battery socket, making sure that the battery terminals are properly aligned.
To power AURATON regulators, we recommend alkaline batteries. Do not use “rechargeable batteries” because the voltage rating is too low.
Mounting of AURATON Aquila R
In order to fix AURATON Aquila R to the wall one should:
- Remove the enclosure (as shown in the “Battery Installation/replacement” section).
- Drill two holes of 6 mm diameter in the wall (the spacing of the holes should be determined by the rear part of the AURATON Aquila R housing).
- Insert the wall plugs into the drilled holes.
- Screw the back part of the AURATON Aquila R housing to the wall using the screws provided.
- Install the batteries and attach the housing.
In the case of a wooden wall, there is no need to use wall plugs. It is enough to drill holes with a diameter of 2.7 mm (instead of 6 mm) and screw the screws directly into the wood.
- Holes for fixing screws.
Alternative mounting methods
AURATON Aquila R can be fixed to a smooth surface using e.g. a double-sided tape. AURATON Aquila R can also be placed anywhere on a level surface using the stand located on the back of the housing.
First start-up of AURATON Aquila R
When the batteries are properly inserted in the sockets, the LCD display will show all segments for a second (display test) followed by the software version number. After a moment, the current temperature is displayed. AURATON Aquila R is ready for operation.
Temperature setting
The first press of any function button always turns on the backlighting, and only the next press calls up the button function.
- Press the b or c button. The segment responsible for the temperature display will go into edit mode, and start flashing.
- Using the b and c buttons, set the desired (setpoint) temperature with an accuracy of 0.2 °C
- Confirm your choice by pressing d briefly
FrostGuard function
AURATON Aquila R is equipped with a special FrostGuard function protecting the room against possible freezing. This function is activated even if AURATON Aquila R is switched off.
With AURATON Aquila R switched off, when the temperature in the room drops to 2 °C, the symbols (!) appear on the display, and a signal is sent to the head, which will switch on the heating. When the temperature rises to 2.2 °C, the display turns off again, and a signal is sent to the head unit to switch off the heating.Set the temporary temperature lowering mode
If you would like to lower the room temperature by 3 °C every day at the same time, there is a possibility of temporary temperature reduction for a period of 6 hours. In order to do this you need to:
- Press and hold both b cbuttons for 3 seconds. The moon symbol (T) will appear on the display.
- AURATON Aquila R enters the temporary temperature lowering mode, and every day at the same time it will reduce the temperature programmed in the normal mode by 3 °C for a period of 6 hours.
After 6 hours, AURATON Aquila R returns to the basic temperature setting. Instead of the moon symbol (T), the sun symbol (S) will appear on the screen.
The “temporary temperature lowering ” mode always starts when the function is activated. This means that a possible temporary temperature reduction should be programmed at the time when we you such a change to take place.
Deactivating the “temporary temperature lowering” mode
To deactivate the “temporary temperature lowering” mode, press the b c buttons again for 3 seconds. The moon (T) or sun (S) symbol will be turned off on the display, and only the room temperature will remain displayed. AURATON Aquila R has returned to normal operation mode.Pairing of AURATON Aquila R daily wireless temperature regulator (transmitter) with AURATON Fornax – wireless regulator of a heating device (receiver)
After connecting to the mains, switch the receiver on by briefly pressing the power button (F). When the device is switched on, the green power diode lights up, and there is an audible single sound signal. To switch off the receiver e.g. outside the heating season, hold down the power button for 3 seconds until there is an audible double sound signal, and the green power diode switches off, which means that the heating device has also been switched off.
The AURATON Aquila R wireless regulator sold together with the AURATON Fornax receiver is already paired. Devices purchased separately require “pairing”.
- Pairing AURATON Aquila R with an AURATON Fornax receiver is initiated by pressing the right pairing button – a single beep (D) on the AURATON Fornax receiver and holding it for at least 3 seconds until the LED starts flashing green (a double beep), then releasing the button.
The AURATON Fornax receiver will wait 120 seconds for pairing. After this time elapses, it will automatically return to normal operation. - On the AURATON Aquila R, press simultaneously the b d or c d buttons for 6 seconds until the transmitting symbol ( W ) lights up on the display.
- Successful completion of pairing is signalled when the green LED diode on the AURATON Fornax receiver is no longer blinking, a single sound signal is heard, and the receiver returns to normal operation.
If there is a pairing error, please repeat steps 1 and 2. In the event of further errors, perform a RESET of the AURATON Fornax receiver (see “RESET – Restoring the AURATON Fornax receiver to factory settings”) and try to pair the AURATON Aquila R again.
The Auraton Fornax receiver can be paired with only one AURATON Aquila R.
Signalling the working status and data package reception
Each reception of radio transmission from paired AURATON Aquila R is signalled by the AURATON Fornax receiver with a momentary alternating change of colour of LED diodes. When the relay is turned on, the LED is red, and when the relay is turned off, the LED is green.
Pressing a button is signalled by a short sound signal.
Unpairing of AURATON Aquila R – daily wireless temperature regulator (transmitter) with AURATON Fornax
- Unpairing of AURATON Aquila R with AURATON Fornax is initiated by pressing the left pairing button (E) on the receiver and holding it for at least 3 seconds, until the LED starts blinking red, then release the button. The sound signalling works in the same way as during pairing, i.e. pressing the button is signalled by a short sound followed by a double short sound signal after 3 seconds.
The AURATON Fornax receiver waits for unpairing of the AURATON Aquila R 120 s. After that time, it automatically returns to normal operation. - Press the b d or c d button simultaneously on the AURATON Aquila R for 6 seconds until the transmit symbol ( W ) lights up on the display.
- Successful completion of unpairing is signalled when the red LED diode on the AURATON Fornax receiver is no longer blinking, a single sound signal is heard, and the receiver returns to normal operation.
If an error occurs during unpairing of AURATON Aquila R, repeat steps 1 and 2. In case further errors occur, perform RESET of AURATON Fornax (see “RESET – Returning AURATON Fornax to factory settings”).
RESET – Returning AURATON Fornax to factory settings
In order to perform a reset to the factory settings in AURATON Fornax, both pairing and deleting buttons (D E) should be pressed simultaneously and held for at least 5 seconds. until LED signalling changes to alternate blinking in green – red colours. Then release both buttons. Sound signals: pressing the button, a short sound signal – after 5 seconds, a double short sound signal.
Successful completion of the reset is signalled after approx. 2 seconds by the change of signalling to green, followed by switching it off for a short time.
If you disconnect AURATON Fornax from the power supply after RESET, and then reconnect the power supply, AURATON Fornax will automatically go into the “pairing” mode for 120 seconds. AURATON Fornax, which is newly purchased (not purchased together with the AURATON Aquila R) without a factory paired regulator, will behave identically.
Hysteresis change
The hysteresis is intended to prevent the executive device from switching on too frequently due to minor temperature fluctuations.
For example, for the HI 2 hysteresis, if the temperature is set to 20 °C, it will be switched on at 19.8 °C and switched off at 20.2 °C. For the HI 4 hysteresis, when the temperature is set to 20 °C, it will be switched on at 19.6 °C and off at 20.4 °C.
HI 2 – ±0,2 °C (factory set)
HI 4 – ±0,4 °C
HI P – PWM mode of operation (chapter “PWM mode of operation”).
Confirm the selection with the d button. AURATON Aquila R will return to normal operation.
PWM working mode
(Pulse-Width Modulation)By changing the hysteresis settings (chapter “Configuration settings”) you can enable the PWM mode.
In this mode, AURATON Aquila R cyclically switches on the heating device in order to minimize temperature fluctuations. AURATON Aquila R checks the times of temperature rise and times of temperature fall.
Knowing these values, the AURATON Aquila R switches the heating device on and off in such cycles as to maintain the temperature as close to the setpoint value as possible.
- Temperature
- Time
- Set temperature
- Room temperature
In the PWM mode, the AURATON Aquila R can switch on the heating device despite the fact that the room temperature is higher than the setpoint temperature. This is due to the PWM algorithm seeking to maintain the setpoint temperature and anticipating the behaviour of the thermal system.
Special cases
- When three consecutive transmissions are lost (after 15 minutes) from AURATON Aquila R, the failure is signalled on the AURATON Fornax receiver (continuous blinking of the LED diode alternately in red and green colours). Until the problem is rectified, the Fornax receiver will go into a memorised on/off cycle of the last 24 hours.
- When the signal from AURATON Aquila R returns, the error is cancelled, and the receiver returns to normal operation.
Additional information and comments
- AURATON Aquila R must be installed at least 1 metre from the Fornax receiver (too strong a signal from the transmitters may cause interference).
- Between successive switching off and on the relay, min. 30 seconds must elapse.
- Data transmission from AURATON Aquila R to AURATON Fornax takes place every time the ambient temperature changes by 0.2°C. If the temperature does not change, AURATON Aquila R transmits control data every 5 minutes (it manifests itself by momentary blinking of diodes on the Fornax receiver – alternately).
- In the event of a power failure, AURATON Fornax will switch off. When power is restored, AURATON Fornax will automatically turn on and wait for the nearest signal from the paired AURATON Aquila R (this signal should arrive no later than 5 minutes after power is restored). When the signal is received, the Fornax receiver will proceed to normal operation.
- Do not place the Fornax receiver in metal housings (e.g. installation box, metal furnace housing) so as not to interfere with AURATON Aquila R operation.
- AURATON Aquila R can be switched on or off at any time by momentarily holding down the d button.
- The first press of any function button always turns on the backlighting, and only the next press calls up the button function.
- When programming any function in AURATON Aquila R, not pressing any button for 10 seconds is equivalent to pressing d.
Cleaning and maintenance
- Clean the outside of the device with a dry cloth. Do not use solvents (such as benzene, thinner or alcohol).
- Do not touch the device with wet hands. It may result in an electric shock or serious damage to the device.
- Do not expose the device to excessive smoke or dust.
- Do not touch the screen with a sharp object.
- Avoid contact of the device with liquids or moisture.
Technical specifications
Power supply: | 2 x AAA (2 x 1.5 V), alkaline |
Working temperature range: | 0 – 45 °C |
Working status signaling: | LCD display |
Number of temperature levels: | 1 |
Anti-freeze temperature: | 2 °C |
Temperature measurement range: | 0 – 35 °C |
Temperature control range: | 5 – 30 °C |
Hysteresis: | ±0.2 °C/±0.4 °C /PWM |
Working cycles: | Daily |
Operation range: | in a typical building with standard wall construction – approx. 30 m; in open space – up to 300 m |
Radio frequency: | 868.850 MHz 869.000 MHz |
Radio signal strength: | Up to 11 dBm |
Level of security: | IP20 |
Dimensions [mm]: | 70 x 70 x 15 |
Disposing of the devices
O
The devices are marked with the crossed-out wheeled bin. According to European Directive 2012/19/EU and the Waste Electrical and Electronic Equipment Act, this kind of marking indicates that the equipment, after its operational life must not be disposed of together with other waste from households.
The user shall return it to a collection point for electrical and electronic waste.
Hereby, LARS Andrzej Szymanski declares that the radio equipment type AURATON Aquila R is in compliance with Directive 2014/53/EU and 2011/65/EU. The full text of the EU declaration of conformity is available in the download section below.
Contact and address of the manufacturer
Lars
ul. Świerkowa 14
64-320 Niepruszewo
Polska
www.auraton.pl